Add support for NUT (EATON inverter)
This commit is contained in:
@@ -0,0 +1,77 @@
|
||||
#!/usr/bin/env bash
|
||||
# Managed by Ansible - DO NOT EDIT MANUALLY
|
||||
#
|
||||
# Wrapper invoked by upsmon as NOTIFYCMD.
|
||||
# upsmon passes the rendered NOTIFYMSG as $1 and sets NOTIFYTYPE in the env.
|
||||
# See: https://networkupstools.org/docs/man/upsmon.conf.html
|
||||
set -euo pipefail
|
||||
|
||||
NTFY_SERVER="{{ nut_ntfy_server }}"
|
||||
NTFY_TOPIC="{{ nut_ntfy_topic }}"
|
||||
{% if nut_ntfy_token is defined %}
|
||||
NTFY_TOKEN="{{ nut_ntfy_token }}"
|
||||
{% else %}
|
||||
NTFY_TOKEN=""
|
||||
{% endif %}
|
||||
|
||||
MESSAGE="${1:-UPS event}"
|
||||
EVENT="${NOTIFYTYPE:-UNKNOWN}"
|
||||
HOST="$(uname -n)"
|
||||
|
||||
case "$EVENT" in
|
||||
ONBATT)
|
||||
TITLE="UPS on battery — $HOST"
|
||||
PRIORITY="urgent"
|
||||
TAGS="warning,electric_plug"
|
||||
;;
|
||||
LOWBATT)
|
||||
TITLE="UPS low battery — $HOST"
|
||||
PRIORITY="urgent"
|
||||
TAGS="rotating_light,battery"
|
||||
;;
|
||||
FSD|SHUTDOWN)
|
||||
TITLE="UPS forced shutdown — $HOST"
|
||||
PRIORITY="max"
|
||||
TAGS="skull"
|
||||
;;
|
||||
ONLINE)
|
||||
TITLE="UPS back on line power — $HOST"
|
||||
PRIORITY="default"
|
||||
TAGS="white_check_mark,zap"
|
||||
;;
|
||||
COMMBAD|NOCOMM)
|
||||
TITLE="UPS communication lost — $HOST"
|
||||
PRIORITY="high"
|
||||
TAGS="warning,satellite"
|
||||
;;
|
||||
COMMOK)
|
||||
TITLE="UPS communication restored — $HOST"
|
||||
PRIORITY="default"
|
||||
TAGS="white_check_mark"
|
||||
;;
|
||||
REPLBATT)
|
||||
TITLE="UPS battery needs replacement — $HOST"
|
||||
PRIORITY="high"
|
||||
TAGS="battery,wrench"
|
||||
;;
|
||||
*)
|
||||
TITLE="UPS event ($EVENT) — $HOST"
|
||||
PRIORITY="default"
|
||||
TAGS="information_source"
|
||||
;;
|
||||
esac
|
||||
|
||||
auth_args=()
|
||||
if [[ -n "$NTFY_TOKEN" ]]; then
|
||||
auth_args=(-H "Authorization: Bearer $NTFY_TOKEN")
|
||||
fi
|
||||
|
||||
# --max-time is important: upsmon will hang on poweroff if curl blocks.
|
||||
curl -fsS --max-time 10 \
|
||||
"${auth_args[@]}" \
|
||||
-H "Title: $TITLE" \
|
||||
-H "Priority: $PRIORITY" \
|
||||
-H "Tags: $TAGS" \
|
||||
-d "$MESSAGE" \
|
||||
"${NTFY_SERVER%/}/${NTFY_TOPIC}" >/dev/null || \
|
||||
logger -t ups-notify "Failed to publish ntfy notification for $EVENT"
|
||||
@@ -0,0 +1,12 @@
|
||||
# Managed by Ansible - DO NOT EDIT MANUALLY
|
||||
# See: https://networkupstools.org/docs/man/ups.conf.html
|
||||
|
||||
[{{ nut_ups_name }}]
|
||||
driver = {{ nut_ups_driver }}
|
||||
port = auto
|
||||
desc = "{{ nut_ups_description }}"
|
||||
pollinterval = {{ nut_ups_pollinterval }}
|
||||
maxretry = {{ nut_ups_maxretry }}
|
||||
{% if nut_ups_vendorid %}
|
||||
vendorid = {{ nut_ups_vendorid }}
|
||||
{% endif %}
|
||||
@@ -0,0 +1,6 @@
|
||||
# Managed by Ansible - DO NOT EDIT MANUALLY
|
||||
# See: https://networkupstools.org/docs/man/upsd.conf.html
|
||||
|
||||
{% for listen in nut_upsd_listen %}
|
||||
LISTEN {{ listen.addr }} {{ listen.port }}
|
||||
{% endfor %}
|
||||
@@ -0,0 +1,6 @@
|
||||
# Managed by Ansible - DO NOT EDIT MANUALLY
|
||||
# See: https://networkupstools.org/docs/man/upsd.users.html
|
||||
|
||||
[{{ nut_monitor_user }}]
|
||||
password = {{ nut_monitor_password }}
|
||||
upsmon master
|
||||
@@ -0,0 +1,37 @@
|
||||
# Managed by Ansible - DO NOT EDIT MANUALLY
|
||||
# See: https://networkupstools.org/docs/man/upsmon.conf.html
|
||||
|
||||
MONITOR {{ nut_ups_name }}@localhost {{ nut_upsmon_minsupplies }} {{ nut_monitor_user }} {{ nut_monitor_password }} master
|
||||
|
||||
MINSUPPLIES {{ nut_upsmon_minsupplies }}
|
||||
SHUTDOWNCMD "{{ nut_upsmon_shutdown_cmd }}"
|
||||
NOTIFYCMD "{{ nut_notify_script_path }}"
|
||||
|
||||
POLLFREQ {{ nut_upsmon_pollfreq }}
|
||||
POLLFREQALERT {{ nut_upsmon_pollfreqalert }}
|
||||
DEADTIME {{ nut_upsmon_deadtime }}
|
||||
HOSTSYNC {{ nut_upsmon_hostsync }}
|
||||
FINALDELAY {{ nut_upsmon_finaldelay }}
|
||||
|
||||
# Default notification messages (overridable per event).
|
||||
NOTIFYMSG ONLINE "UPS %s is back on line power"
|
||||
NOTIFYMSG ONBATT "UPS %s is on battery (mains lost)"
|
||||
NOTIFYMSG LOWBATT "UPS %s battery is low — shutdown imminent"
|
||||
NOTIFYMSG FSD "UPS %s forced shutdown in progress"
|
||||
NOTIFYMSG COMMOK "Communications with UPS %s restored"
|
||||
NOTIFYMSG COMMBAD "Communications with UPS %s lost"
|
||||
NOTIFYMSG SHUTDOWN "System is shutting down due to UPS %s"
|
||||
NOTIFYMSG REPLBATT "UPS %s battery needs replacement"
|
||||
NOTIFYMSG NOCOMM "UPS %s is unavailable"
|
||||
|
||||
# Route events through SYSLOG and the NOTIFYCMD wrapper. NUT also supports
|
||||
# WALL (broadcast to logged-in users) but it's noisy and not useful here.
|
||||
NOTIFYFLAG ONLINE SYSLOG+EXEC
|
||||
NOTIFYFLAG ONBATT SYSLOG+EXEC
|
||||
NOTIFYFLAG LOWBATT SYSLOG+EXEC
|
||||
NOTIFYFLAG FSD SYSLOG+EXEC
|
||||
NOTIFYFLAG COMMOK SYSLOG+EXEC
|
||||
NOTIFYFLAG COMMBAD SYSLOG+EXEC
|
||||
NOTIFYFLAG SHUTDOWN SYSLOG+EXEC
|
||||
NOTIFYFLAG REPLBATT SYSLOG+EXEC
|
||||
NOTIFYFLAG NOCOMM SYSLOG+EXEC
|
||||
Reference in New Issue