@@ -0,0 +1,77 @@
#!/usr/bin/env bash
# Managed by Ansible - DO NOT EDIT MANUALLY
#
# Wrapper invoked by upsmon as NOTIFYCMD.
# upsmon passes the rendered NOTIFYMSG as $1 and sets NOTIFYTYPE in the env.
# See: https://networkupstools.org/docs/man/upsmon.conf.html
set -euo pipefail
NTFY_SERVER="{{ nut_ntfy_server }}"
NTFY_TOPIC="{{ nut_ntfy_topic }}"
{% if nut_ntfy_token is defined %}
NTFY_TOKEN="{{ nut_ntfy_token }}"
{% else %}
NTFY_TOKEN=""
{% endif %}
MESSAGE="${1:-UPS event}"
EVENT="${NOTIFYTYPE:-UNKNOWN}"
HOST="$(uname -n)"
case "$EVENT" in
ONBATT)
TITLE="UPS on battery — $HOST"
PRIORITY="urgent"
TAGS="warning,electric_plug"
;;
LOWBATT)
TITLE="UPS low battery — $HOST"
PRIORITY="urgent"
TAGS="rotating_light,battery"
;;
FSD|SHUTDOWN)
TITLE="UPS forced shutdown — $HOST"
PRIORITY="max"
TAGS="skull"
;;
ONLINE)
TITLE="UPS back on line power — $HOST"
PRIORITY="default"
TAGS="white_check_mark,zap"
;;
COMMBAD|NOCOMM)
TITLE="UPS communication lost — $HOST"
PRIORITY="high"
TAGS="warning,satellite"
;;
COMMOK)
TITLE="UPS communication restored — $HOST"
PRIORITY="default"
TAGS="white_check_mark"
;;
REPLBATT)
TITLE="UPS battery needs replacement — $HOST"
PRIORITY="high"
TAGS="battery,wrench"
;;
*)
TITLE="UPS event ($EVENT) — $HOST"
PRIORITY="default"
TAGS="information_source"
;;
esac
auth_args=()
if [[ -n "$NTFY_TOKEN" ]]; then
auth_args=(-H "Authorization: Bearer $NTFY_TOKEN")
fi
# --max-time is important: upsmon will hang on poweroff if curl blocks.
curl -fsS --max-time 10 \
"${auth_args[@]}" \
-H "Title: $TITLE" \
-H "Priority: $PRIORITY" \
-H "Tags: $TAGS" \
-d "$MESSAGE" \
"${NTFY_SERVER%/}/${NTFY_TOPIC}" >/dev/null || \
logger -t ups-notify "Failed to publish ntfy notification for $EVENT"
+12
View File
@@ -0,0 +1,12 @@
# Managed by Ansible - DO NOT EDIT MANUALLY
# See: https://networkupstools.org/docs/man/ups.conf.html
[{{ nut_ups_name }}]
driver = {{ nut_ups_driver }}
port = auto
desc = "{{ nut_ups_description }}"
pollinterval = {{ nut_ups_pollinterval }}
maxretry = {{ nut_ups_maxretry }}
{% if nut_ups_vendorid %}
vendorid = {{ nut_ups_vendorid }}
{% endif %}
+6
View File
@@ -0,0 +1,6 @@
# Managed by Ansible - DO NOT EDIT MANUALLY
# See: https://networkupstools.org/docs/man/upsd.conf.html
{% for listen in nut_upsd_listen %}
LISTEN {{ listen.addr }} {{ listen.port }}
{% endfor %}
+6
View File
@@ -0,0 +1,6 @@
# Managed by Ansible - DO NOT EDIT MANUALLY
# See: https://networkupstools.org/docs/man/upsd.users.html
[{{ nut_monitor_user }}]
password = {{ nut_monitor_password }}
upsmon master
+37
View File
@@ -0,0 +1,37 @@
# Managed by Ansible - DO NOT EDIT MANUALLY
# See: https://networkupstools.org/docs/man/upsmon.conf.html
MONITOR {{ nut_ups_name }}@localhost {{ nut_upsmon_minsupplies }} {{ nut_monitor_user }} {{ nut_monitor_password }} master
MINSUPPLIES {{ nut_upsmon_minsupplies }}
SHUTDOWNCMD "{{ nut_upsmon_shutdown_cmd }}"
NOTIFYCMD "{{ nut_notify_script_path }}"
POLLFREQ {{ nut_upsmon_pollfreq }}
POLLFREQALERT {{ nut_upsmon_pollfreqalert }}
DEADTIME {{ nut_upsmon_deadtime }}
HOSTSYNC {{ nut_upsmon_hostsync }}
FINALDELAY {{ nut_upsmon_finaldelay }}
# Default notification messages (overridable per event).
NOTIFYMSG ONLINE "UPS %s is back on line power"
NOTIFYMSG ONBATT "UPS %s is on battery (mains lost)"
NOTIFYMSG LOWBATT "UPS %s battery is low — shutdown imminent"
NOTIFYMSG FSD "UPS %s forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s restored"
NOTIFYMSG COMMBAD "Communications with UPS %s lost"
NOTIFYMSG SHUTDOWN "System is shutting down due to UPS %s"
NOTIFYMSG REPLBATT "UPS %s battery needs replacement"
NOTIFYMSG NOCOMM "UPS %s is unavailable"
# Route events through SYSLOG and the NOTIFYCMD wrapper. NUT also supports
# WALL (broadcast to logged-in users) but it's noisy and not useful here.
NOTIFYFLAG ONLINE SYSLOG+EXEC
NOTIFYFLAG ONBATT SYSLOG+EXEC
NOTIFYFLAG LOWBATT SYSLOG+EXEC
NOTIFYFLAG FSD SYSLOG+EXEC
NOTIFYFLAG COMMOK SYSLOG+EXEC
NOTIFYFLAG COMMBAD SYSLOG+EXEC
NOTIFYFLAG SHUTDOWN SYSLOG+EXEC
NOTIFYFLAG REPLBATT SYSLOG+EXEC
NOTIFYFLAG NOCOMM SYSLOG+EXEC